| Motor output | Ventilation amount (in case of air cooling) | Cooling tower (in case of water cooling) |
||
|---|---|---|---|---|
| Heat amount generated (MJ/h) |
Exhausted air amount (m3/min) |
If t = 5 (m3/min) |
CT exit temperature, if 32ºC |
|
| 7.5kW | 32 | 20 | 85 | |
| 11kW | 47 | 30 | 125 | |
| 15kW | 68 [54] |
45 [85] (80)*3 |
180 [145] |
5t over |
| 22kW | 97 [79] |
55 [105] (80)*3 |
260 [210] |
10t over |
| 30kW | (121)*3 | (100)*3 | (340)*3 | |
| 37kW | 159 [130] |
85 [200] (120)*3 |
430 [400] |
10t over |
| 45kW | (184)*3 | (150)*3 | (510)*3 | |
| 55kW | 201 [Please ask us] |
140 [Please ask us] |
880 [Please ask us] |
15t over |
| 75kW | 272 [Please ask us] |
190 [Please ask us] |
1,200 [Please ask us] |
20t over |
| 90kW | 30t over | |||
| 100kW | 30t over | |||
| 120kW | 30t over | |||
| 150kW | 30t over | |||
The figures in [ ] are those of ZU and ZUV.
(Please ask us or the designated service factory about the details)
*3: Applied to i-14000 IPM motor machine.