| Motor output | Breaker | Transformer | Secondary cable | Grounding | ||
|---|---|---|---|---|---|---|
| No-fuse breaker | Power supply transformer capacity | If 22kW or less, within 10m | If 37kW or more, within 20m | Cable diameter Terminal screw diameter | ||
| 200/220V | 400/440V | 200/220V | 400/440V | |||
| 7.5kW | 100AF-60AT (100AF-60AT) |
30AF-30AT (30AF-30AT) |
10KVA (17KVA) |
8mm2 M 5 (14mm2 M 5) |
3.5mm2 M 4 (3.5mm2 M 4) |
5.5mm2 M 4 |
| 11kW | 100AF-75AT (100AF-75AT) |
50AF-50AT (50AF-50AT) |
15KVA (20KVA) |
14mm2 M 5 (14mm2 M 5) |
5.5mm2 M 4 (5.5mm2 M 6) |
14mm2 M 5 |
| 15kW | 100AF-100AT (225AF125AT) (100AF-100AT)*3 |
100AF-60AT (100AF-60AT) |
20KVA (28KVA) (20kVA)*3 |
22mm2 M 8 (38mm2 M 6) (22mm2 M6)*3 |
14mm2 M 5 (14mm2 M 5) |
14mm2 M 5 (14mm2 M6)*3 |
| 22kW | NF225-*-175AT (225AF-175AT)*1 (225AF-150AT)*2 |
100AF-100AT (100AF-100AT)*1 |
30KVA (41KVA) (32kVA)*3 |
38mm2 M10 (38mm2 M 10) |
22mm2 M 8 (22mm2 M 8) |
22mm2 M 8 (22mm2 M6)*3 |
| 30kW | (225AF-175AT)*3 | - | (42kVA)*3 | (60mm2 M8)*3 | - | (38mm2 M6)*3 |
| 37kW | NF225-*-225AT (400AF-300AT)*1 (225AF-225AT)*2 |
225AF-150AT (225AF-175AT)*1 |
50KVA (80KVA) (52kVA)*3 |
100mm2 M10 (100mm2 M10) (80mm2 M10)*3 |
38mm2 M 8 (38mm2 M 8) |
22mm2 M 8 (38mm2 M8)*3 |
| 45kW | (400AF-300AT)*3 | - | (63kVA)*3 | (100mm2 M10)*3 | - | (60mm2 M8)*3 |
| 55kW | NF400-*-400AT (400AF-350AT) |
NF225-*-225AT (225AF-175AT)*1 |
75KVA (74KVA) |
150mm2 M12 (150mm2 M12) |
60mm2 M10 (60mm2 M 8) |
38mm2 M 8 |
| 75kW | NF400-*-400AT (400AF-400AT) |
NF225-*-225AT (225AF-225AT)*1 |
150KVA (110KVA) |
200mm2 M12 (200mm2 M12) |
60mm2 M10 (60mm2 M12) |
38mm2 M 8 |
| 90kW | - | 400AF-350AT | 150KVA | 200mm2 M12 | 150mm2 M12 | 38mm2 M 8 |
| 100kW | - | 400AF-400AT | 150KVA | 325mm2 M12 | 150mm2 M12 | 38mm2 M 8 |
| 120kW | - | 400AF-400AT | 200KVA | 325mm2 M12 | 200mm2 M12 | 60mm2 M10 |
| 150kW | - | NF400-*-400AT | 300KVA | 325mm2 M12 | 250mm2 M12 | 60mm2 M10 |
Figures in ( ) are that of inverter specifications.
* (SEW or HEW) Please use breakers we recommend (made by Mitsubishi Electric Co., Ltd.) (if changed in the same frame).
*1: Applied to type 1.
*2: Applied to type 2 (IPM motor machine).
*3: Applied to i-14000 IPM motor machine.